Technical Data
Power Supply:
- Operating Voltage: +24 V
- Current Consumption (Depending on Configuration):
- Basic Requirement: 140 mA
- Additional for Each Function Unit When Transmitter Active:
- NAMUR: 9 mA contacts, 24 V
- 17 mA contacts, 48 V
- 7 mA + meas. current 2-wire-transducer
- Reference Potential: 0 V
- Power Dissipation: 3.4 ... 11 W depending on operating voltage and configuration
- Approximation Formula: approx. 3.4 W + 24 V * (n * current per function unit when the transmitter is active), where n = number of function units configured
Binary Transmitter Mode:
- Single/changeover contacts with 48 V supply from the module, with/without monitoring
- Input Values:
- 0-signal without monitor: 0 ... 10.5 V
- 0-signal with monitor: 6 ... 10.5 V
- 1-signal: 14 ... 51 V
- Response Range of Monitor: 0 ... 3 V
- Input Resistance: 10 kOhm + 11 %, - 10 %
- Destruction Limit: > 55 V
- Resistance (Forward and Return Lines): 5 ... 100 Ohm
- Output Values:
- Output Voltage: 48 V +1- 5
- Output Current: max. 32 mA
- Response Time of Monitoring Function: 0.5 sec (for use with monitoring)
- Input Values:
- 0-signal: 0 ... 3 V
- 1-signal: 11.2 ... 30 V
- Input Resistance: 15 kOhm + 13 %, - 10 %
- Destruction Limit: > 65 V
- Resistance (Forward and Return Lines): 5 ... 100 Ohm
- Output Values:
- Output Voltage: US - 5.5 V
- Output Current: max. 50 mA
Binary Transmitter Mode:
- 0-signal: 0 ... 3 V
- 1-signal: 11.2 ... 60 V
- Input Resistance: 15 kOhm + 13 %, - 10 %
- Static Potential Difference Compared to Reference Potential: < 0.5 V of external power supply
- Destruction Limit: > 65 V
- Resistance (Forward and Return Lines): 5 ... 100 Ohm
Inductive Initiators acc. to NAMUR (DIN 19234), Supply from Module, with Monitor:
- Input Values:
- Signal Change at Short-Circuit Alarm: 1.65 mA
- Open-Circuit Alarm: ≥ 6 mA
- Input Resistance: 50.35 mA
- Destruction Limit: > 12 V
- Resistance (Forward and Return Lines): 5 ... 50 Ohm
- Output Values:
- Output Voltage: 8.2 ... 10 V
- Output Current: max. 10 mA
Analog Transmitter Mode:
- Input Values:
- Input Current, Nominal Signal Range: 0 ... 20 mA (corresponds to 0 ... 100 %)
- Signal Range: 4 ... 20 mA
- Maximum Range: -1 ... 30 mA
- Measuring Resistor: 50 Ohm
- Destruction Limits: ± 50 mA
- Resistance (Forward and Return Lines): 5 ... 100 Ohm
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...