ABB UR600IR Flame Scanner
-
Sensor: PbS (Lead Sulphide)
-
Spectrum Sensitivity: 0.6 ÷ 3 μm
-
Power Consumption: 300 mW DC supplied by Uvisor series control units
-
Ambient Temperature:
- Operating: -10 ÷ 80°C (14 ÷ 176 °F)
- T6 classified area: Max. 60°C (140 °F)
- Storage: -40 ÷ 100°C (-40 ÷ 212 °F)
-
Enclosure: IP66 (NEMA 4X)
-
Classification: EEx-d IIC T6, ATEX category G-D CE type examination Certificate CESI 03 ATEX 151
-
Dimensions: 94 x 94 x 172 mm
-
Weight: 1 Kg (2.2 Lbs)
-
Air for Lens Cleaning: From clean ambient
-
Air Flow for Lens Cleaning:
- Direct View: 115 l/min (4 SCFM). Excessive contaminant fuels might require up to 400 l/min (14 SCFM).
- Extended Probe: 400 l/min (14 SCFM).
-
Minimum Cleaning Air Pressure:
- Direct View: 20 mm H2O (1" W.C.) above the max wind box pressure measured at the “y” connection inlet.
- Extended Probe: 300 mm H2O (12" W.C.) above the max wind box pressure measured at the “y” connection inlet
-
Maximum Fiber Optic Continuous Operating Temperature: 350°C (662°F)
-
Mounting Connection: 1" NPT male thread
-
Cable Entry for Electrical Connection: 1/2" NPT female thread
-
Electrical Connections: Standard 4 x 0.55 sq.mm (20 AWG) shielded cable. Recommended max. 300 meters (1000 feet) length. Screw type termination.
-
Compatible Amplifier Unit: Uvisor series amplifier
-
Approvals: CE ATEX FM in progress CSA in progress
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...