The specifications for the GE EPXPNS001 system:
System Data:
-
Connection: 2 x RJ-45
-
Fieldbus Protocol: PROFINET Version 2.3 Class C I/O Device (IRT, RT)
-
Process Image:
- Input Data Width: Max. 512 bytes
- Output Data Width: Max. 512 bytes
- Parameter Data: Max. 4362 bytes
- Diagnostic Data: Max. 1408 bytes
-
Number of Modules: Max. 64 active
-
Configuration Interface: Micro USB 2.0
-
Transfer Rate:
- Fieldbus: Max. 100 Mbps
- RSTi-EP System Bus: Max. 48 Mbps
-
Data Format: Default: Motorola; Configurable: Intel
-
PROFINET I/O Update Rate: Configurable selections: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms, and 512ms
-
Supports MRP: Yes
- Minimum I/O Update Rate for bumpless operation in an MRP ring topology is 32ms and slower for EPXPNS001
Supply:
-
Supply Voltage for System and Inputs: 20.4V – 28.8V
-
Supply Voltage for Outputs: 20.4V – 28.8V
-
Max. Feed-in Current for Input Modules: 10 A
-
Max. Feed-in Current for Output Modules: 10 A
-
Current Consumption from System Current Path ISYS: 116 mA
Connection Data:
-
Type of Connection: Spring style
-
Conductor Cross-Section: Single-wired, fine-wired 0.14 – 1.5 mm² (AWG 26 – 16)
General Data:
-
Operating Temperature: -20°C to +60°C (-4°F to +140°F)
-
Storage Temperature: -40°C to +85°C (-40°F to +185°F)
-
Air Humidity (Operation/Transport): 5% to 95%, non-condensing as per DIN EN 61131-2
-
Width: 52 mm (2.05 in)
-
Depth: 76 mm (2.99 in)
-
Height: 120 mm (4.72 in)
-
Weight: 220 g (7.76 oz)
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...