Technical specification:
Master Reset Password:
- Length: 8 to 10 alphanumeric characters
Settings Password:
- Length: 3 to 10 alphanumeric characters
- Purpose: Local and remote access
Control Password:
- Length: 3 to 10 alphanumeric characters
- Purpose: Local and remote access
Overcurrent Settings
Phase/Neutral/Ground/Negative Sequence Time Overcurrent (51P/51N/51G/51_2):
-
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 x CT
-
Dropout Level:
- 97% of Pickup @ I > 1 x CT
- 0.02 x CT @ I < 1 x CT
-
Curve Shape:
- ANSI: Extremely/Very/Moderately/Normally Inverse
- Definite Time: 0.1 s base curve
- IEC: Curve A/B/C/Short Inverse
- IAC: Extreme/Very/Inverse/Short Inverse
- User Curve: FlexCurve™ A/B (programmable curves)
-
Curve Multiplier: 0.05 to 50.00 in steps of 0.01
-
Reset Time: Instantaneous, Linear Time Delay
-
Accuracy:
- ±3% of expected inverse time or 1.5 cycle, whichever is greater, from pickup to operate
-
Level Accuracy: Per CT input
Sensitive Ground Time Overcurrent (51SG)
-
Pickup Level: 0.005 to 3.000 x CT in steps of 0.001 x CT
-
Dropout Level:
- 97% of Pickup @ I > 0.1 x CT
- 0.002 x CT @ I < 0.1 x CT
-
Curve Shape:
- ANSI: Extremely/Very/Moderately/Normally Inverse
- Definite Time: 0.1 s base curve
- IEC: Curve A/B/C/Short Inverse
- IAC: Extreme/Very/Inverse/Short Inverse
- User Curve: FlexCurve™ A/B
-
Curve Multiplier: 0.05 to 50.00 in steps of 0.01
-
Reset Time: Instantaneous, Linear Time Delay
-
Accuracy:
- ±3% of expected inverse time or 1 cycle, whichever is greater, from pickup to operate
-
Level Accuracy: Per CT input
Instantaneous Overcurrent Settings
Phase/Neutral/Ground/Negative Sequence Instantaneous Overcurrent (50P/50N/50G/50_2):
-
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 x CT
-
Dropout Level:
- 97% of Pickup @ I > 1 x CT
- 0.02 x CT @ I <1 x CT
-
Time Delay: 0.00 to 300.00 sec in steps of 0.01
-
Operate Time:
- <30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
- <35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
-
Time Delay Accuracy:
- 1% or 1 cycle, whichever is greater (Time Delay selected)
-
Level Accuracy: Per CT input
Sensitive Ground Instantaneous Overcurrent (50SG)
-
Pickup Level: 0.005 to 3.000 x CT in steps of 0.001 x CT
-
Dropout Level:
- 97% of Pickup @ I > 0.1 x CT
- 0.002 x CT @ I < 0.1 x CT
-
Time Delay: 0.00 to 300.00 sec in steps of 0.01
-
Operate Time:
- <30 ms @ 60Hz (I > 2.0 x PKP, No time delay)
- <35 ms @ 50Hz (I > 2.0 x PKP, No time delay)
-
Time Delay Accuracy:
- 1% or 1 cycle, whichever is greater (Time Delay selected)
-
Level Accuracy: Per CT input
Phase Directional (67P)
-
Directionality: Co-existing forward and reverse
-
Operating: Phase Current (Ia, Ib, Ic)
-
Polarizing Voltage: Quadrature Voltage
- ABC phase sequence: Vbc, Vca, Vab
- CBA phase sequence: Vcb, Vac, Vba
-
Polarizing Voltage Threshold: 0.05 to 1.25 x VT in steps of 0.01
-
MTA: From 0º to 359º in steps of 1°
-
Angle Accuracy: ±4º
-
Operation Delay: 20 to 30 ms
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...
Contact Information