Frequently inquire Together
100% Genuine Stock, 24/7 Service
InquiryTechnical Specifications
PROTECTION
PHASE/NEUTRAL AND GROUND TIMED OVERCURRENT (51PH/51PL/51N/51G)
- Current: Fundamental Phasor (without harmonics) or RMS
- Rated current: For connection to 1 or 5 A CTs
- Pickup level: 0.05 to 160.00 A in steps of 0.01 A
- Reset Dropout level: 97% to 98% of the pickup level
- Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10A; ±1.5% of the reading for values higher than 10A
Operation Curves
- IEEE extremely/very/moderately inverse
- IEC Curve A/B/C/Long-Time Inverse/Short-Time Inverse
- ANSI extremely/very/normally/moderately inverse
- I2t
- IAC extremely/very/moderately inverse
- Definite time
- Rectifier curve
- User curve FlexCurve™ A/B/C/D
Reset Time Type
- Instantaneous or time delayed according to IEEE
Snapshot Events
- Selectable by setting
Timer Accuracy
- From 1.03 times the pickup, ±3% of operation time or 50 ms. (whichever is greater)
Voltage Restraint
- Selectable by setting
NEGATIVE SEQUENCE (46)
- Current: Fundamental phasor (without harmonics)
- Pickup level: 0.05 to 160.00 A in steps of 0.01 A
- Reset level: 98% of the pickup level
- Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10A; ±1.5% of the reading for higher values
Operation Curves
- IEEE extremely/very/moderately inverse
- IEC Curve A/B/C/Long-Time Inverse/Short-Time Inverse
- ANSI extremely/very/normally/moderately inverse
- I2t
- IAC extremely/very/moderately inverse
- Definite time
- Rectifier curve
- User curve FlexCurve™ A/B/C/D
Reset Time Type
- Instantaneous or time delayed according to IEEE
Timing
- Operate at > 1.03 times the pickup ±3% of operate time or 50 ms. (whichever is greater)
SENSITIVE GROUND TIMED OVERCURRENT (51SG)
- Current: Fundamental Phasor (without harmonics) or RMS
- Rated current: For connection to 1 or 5 A CTs
- Pickup level: 0.005 to 16.00 A in steps of 0.001 A
- Reset dropout level: 97% to 98% of the pickup level
- Accuracy: ±1.5% of the reading ±1 mA from 0.005 to 16 A
Operation Curves
- IEEE extremely/very/moderately inverse
- IEC Curve A/B/C/Long-Time Inverse/Short-Time Inverse
- IAC extremely/very/normally/moderately inverse
- ANSI extremely/very/normally/moderately inverse
- I2t
- Definite time
- Rectifier curve
- FlexCurve™ A/B/C/D user curve
Reset Time
- Instantaneous or time delayed according to IEEE
Timing Accuracy
- Operate at > 1.03 times the pickup ±3% of operate time or 50 ms. (whichever is greater)
PHASE/NEUTRAL AND GROUND INSTANTANEOUS OVERCURRENT (50PH/50PL/50N/50G)
- Current: Fundamental Phasor (without harmonics) or RMS
- Rated current: For connection to 1 or 5 A CTs
- Pickup level: 0.05 to 160.0 A in steps of 0.01
- Reset dropout level: 97% to 98% of the pickup level
- Accuracy: ±0.5% of the reading ±10mA from 0.05 to 10A; ±1.5% of the reading for higher values
- Overreach < 2%
- Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s.
- Operate time: <30 ms at 3 x Pickup at 50 Hz, typically
- Reset time delay: 0.00 to 900.00 s. in steps of 0.01 s.
- Timing accuracy: at 0ms time delay (no intentional delay): 50 ms; at non-zero time delay: ±3% of operate time or 50 ms (whichever is greater)
Is our price competitive?
What is the warranty period?
What payment methods do we accept?
What is the warranty period?
What shipping methods do we use?
What is our delivery time?
How do we package the goods?
How can customers contact us and request a quote?
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...
Contact Information
- Email: sales7@cambia.cn
- TEL: +86 180 3027 3592