Technical Specifications
SENSITIVE GROUND INSTANTANEOUS OVERCURRENT (50SG)
- Current: Fundamental Phasor (without harmonics) or RMS
- Rated current: For connection to 1 or 5 A CTs
- Pickup level: 0.005 to 16.0 A in steps of 0.001 A
- Reset dropout level: 97% to 98% of the pickup level
- Accuracy: ±1.5% of the reading ±1 mA from 0.005 to 16 A
- Overreach: < 2%
- Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s.
- Operate Time: < 30 ms at 3 x Pickup at 50 Hz
- Reset time: 0.00 to 900.00 s. in steps of 0.01 s.
- Timing accuracy: at 0ms time delay (no intentional delay): 50 ms; at non-zero time delay: ±3% of operate time or 50 ms (whichever is greater)
ISOLATED GROUND INSTANTANEOUS OVERCURRENT (50IG)
- Current Input: Fundamental Phasor (without harmonics)
- Voltage Input: Fundamental Phasor (without harmonics)
- Current Pickup level: 0.005 to 0.400 A in steps of 0.001 A
- Voltage Pickup level: 2 to 70 V in steps of 1 V
- Dropout level: 97 to 98% of the pickup level
- Level Accuracy: ±1.5% of the reading ±1 mA from 0.005 to 16 A
- Trip delay: 0.00 to 900.00 s. in steps of 0.01 s.
- Operate time: <50 ms at 3 x Pickup at 50 Hz, typically
- Timing accuracy: at 0ms time delay (no intentional delay): 50 ms; at non-zero time delay: ±3% of operate time or 50 ms (whichever is greater)
- Snapshot Events: Selectable by setting
PHASE DIRECTIONAL UNITS (67P)
- Directionality: Forward and reverse selectable by setting
- Polarizing: Quadrature Voltage
- ABC seq: Phase A (VBC), Phase B (VCA), Phase C (VAB)
- ACB seq: Phase A (VCB), Phase B (VAC), Phase C (VBA)
- Polarizing voltage threshold: 0 to 300 Vac in steps of 1 V
- Current Sensitivity Threshold: 50 mA
- Characteristic angle: -90º to +90º in steps of 1º
- Block Logic: Permission or Block selectable by setting
- Angle accuracy: ±2º for I>0.1 A and V>5 Vac
- Operate time: <30ms, typically
NEUTRAL AND GROUND DIRECTIONAL UNIT (67N/67G)
- Directionality: Forward and reverse selectable by setting
- Polarizing: Voltage, current, dual
- Polarizing Voltage: VN (measured or calculated, selected by setting)
- Polarizing Current: Isg (measured from 5th current transformer)
- Operating Current: Ig (measured from 4th current transformer)
- Polarizing Voltage threshold: 0 to 300 Vac in steps of 1 V
- Polarizing Current threshold: 0.005 A
- Characteristic angle: -90º to +90º in steps of 1º
- Block Logic: Permission or Block selectable by setting
- Angle accuracy: ±2º for I>0.1 A and V>5 Vac
- Operate time: <30ms, typically
SENSITIVE GROUND DIRECTIONAL UNIT (67SG)
- Polarization By: Voltage
- Polarization Voltage: 0 to 300 Vac in steps of 1V
- Directionality: Forward and reverse selectable by setting
- Characteristic angle: -90º to +90º in steps of 1º
- Angle accuracy: ±3º from 0.1 A and 5 Vac
- Response time: <30ms typically
THERMAL MODEL (49)
- Current: Fundamental phasor (without harmonics)
- Rated current: Valid for connection to 1 or 5 A CTs
- Pickup level: 0.05 to 160.00 A in steps of 0.01 A
- Dropout level: 97% to 98% of the pickup
- Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10 A; ±1.5% of the reading for higher values
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...