The technical specifications for GE Multilin T60 Comprehensive Three-phase Transformer Relay:
Percent Differential:
- Characteristic: Differential Restraint pre-set
- Number of Zones: 2
- Minimum Pickup: 0.05 to 1.00 pu
- Slope 1 range: 15 to 100%
- Slope 2 range: 50 to 100%
- Kneepoint 1: 1.0 to 4.0 pu
- Kneepoint 2: 4.0 to 30.0 pu
- 2nd Harmonic Inhibit Range: 1.0 to 40.0%
- 5th Harmonic Inhibit Range: 1.0 to 40.0%
- Operate Times:
- Harmonic Inhibits Selected: 20 to 30 ms
- No Harmonic Inhibits Selected: 5 to 20 ms
- Dropout Level: 97 to 98% of pickup
- Level Accuracy: ±0.5% of reading or ±1% of rated
Instantaneous Differential:
- Pickup Level: 2.00 to 30.00 pu
- Dropout Level: 97 to 98% of pickup
- Level Accuracy: ±0.5% of reading or ±1% of rated
- Operate Time: < 20 ms at 3 × pickup at 60 Hz
Restricted Ground Fault:
- Minimum Pickup: 0.000 to 30.000 pu
- Dropout Level: 97 to 98% of Pickup
- Slope Range: 0 to 100%
- Pickup Delay: 0 to 600.00 s
- Dropout Delay: 0 to 600.00 s
- Operate Time: 15 to 35 ms at 0 ms time delay
Phase/Neutral/Ground TOC:
- Current: Phasor or RMS
- Pickup Level: 0.000 to 30.000 pu
- Dropout Level: 97% to 98% of Pickup
- Level Accuracy: ±0.5% of reading or ±1% of rated
- Curve Shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse, Short/Very/Extremely Inverse; I2t; FlexCurve™ (programmable); Definite Time (0.01 s base curve)
- Curve Multiplier: Time Dial = 0.00 to 600.00
- Reset Type: Instantaneous/Timed (per IEEE)
Phase/Neutral/Ground IOC:
- Pickup Level: 0.000 to 30.000 pu
- Dropout Level: 97 to 98% of Pickup
- Level Accuracy: 0.1 to 2.0 × CT rating: ±0.5% of reading or ±1% of rated; > 2.0 × CT rating ±1.5% of reading
- Overreach: <2%
- Pickup Delay: 0.00 to 600.00 s
- Reset Delay: 0.00 to 600.00 s
- Operate Time: <20 ms at 3 × Pickup at 60 Hz
- Timing Accuracy: Operate at 1.5 × Pickup ±3% or ±4 ms (whichever is greater)
Phase Directional Overcurrent:
- Relay Connection: 90° (quadrature)
- Quadrature Voltage: ABC Phase Seq. and ACB Phase Seq.
- Polarizing Voltage Threshold: 0.000 to 3.000 pu
- Current Sensitivity Threshold: 0.05 pu
- Characteristic Angle: 0 to 359°
- Angle Accuracy: ±2°
- Operation Time (FlexLogic™ Operands): Tripping < 12 ms, Blocking < 8 ms
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...