Technical Specifications:
Undervoltage Monitoring:
-
Required Voltage: 20 V applied
-
Pickup Level: 0.50 – 0.99 x VT in steps of 0.01
-
Dropout Level: 103% of pickup
-
Time Delay: 0.5 – 600.0 sec in steps of 0.5 sec
-
Phases: Programmable for any one, any two, or all three phases
-
Level Accuracy: Per voltage input
-
Timing Accuracy: -0/+1 sec
Overvoltage Monitoring:
-
Pickup Level: 1.01 – 1.25 x VT in steps of 0.01
-
Dropout Level: 97% of pickup
-
Time Delay: 0.5 – 600.0 sec in steps of 0.5 sec
-
Phases: Programmable for any one, any two, or all three phases
-
Level Accuracy: Per voltage input
-
Timing Accuracy: -0/+1 sec
Underfrequency Monitoring:
-
Required Voltage: 20 V applied
-
Pickup Level: 20 – 70.00 Hz in steps of 0.01 Hz
-
Dropout Level: Pickup +0.03 Hz
-
Time Delay: 0.1 – 10.0 sec in steps of 0.1 sec
-
Level Accuracy: ±0.02 Hz
-
Timing Accuracy: ±3 cycles
Overfrequency Monitoring:
-
Required Voltage: 20 V applied
-
Pickup Level: 20 – 70.00 Hz in steps of 0.01 Hz
-
Dropout Level: Pickup -0.03 Hz
-
Time Delay: 0.1 – 10.0 sec in steps of 0.1 sec
-
Level Accuracy: ±0.02 Hz
-
Timing Accuracy: ±3 cycles
Power Factor Monitoring:
-
Required Voltage: 20 V applied
-
Pickup Level: 0.50 lag – 0.50 lead in steps of 0.01
-
Dropout Level: 0.50 lag – 0.50 lead in steps of 0.01
-
Time Delay: 0.5 – 600.0 sec in steps of 0.5 sec
-
Timing Accuracy: -0/+1 sec
Power Supply
Control Power:
-
Input: 90 – 300 VDC or 70 – 265 VAC, 50/60 Hz
-
Power: 10 VA nominal, 20 VA maximum
-
Holdup: 100 ms typical @ 120 VAC/VDC
Outputs
Analog Outputs:
-
Accuracy: ±1% of full scale reading
-
Output Options:
- 0 – 1 mA
- 0 – 20 mA
- 4 – 20 mA (T20 Option)
-
Max Load:
- 2400 Ω (0 – 1 mA)
- 600 Ω (0 – 20 mA)
-
Max Output:
-
Isolation: 50 V isolated, active source
Output Relays:
-
Voltage:
-
Make/Carry Continuous: 5 A
-
Make/Carry 0.2 Sec: 30 A
-
Break: Varies by voltage and load type
-
Resistive Load Ratings:
- 30 VDC: 5 A
- 125 VDC: 5 A
- 250 VDC: 5 A
- 120 VAC: 5 A
- 250 VAC: 5 A
-
Inductive Load Ratings (Vr = 7 ms):
- 30 VDC: 5 A
- 125 VDC: 5 A
- 250 VDC: 5 A
- 120 VAC: 5 A
- 250 VAC: 5 A
- PF = 0.4: 5 A
-
Configuration: FORM C NO/NC
-
Contact Material: Silver alloy
Pulse Output:
-
Parameters: +ve kWh, -ve kWh, +ve kvarh, -ve kvarh, kVAh
-
Interval: 1 – 65000 in steps of 1
-
Pulse Width: 100 – 2000 ms in steps of 10 ms
-
Min Pulse Interval: 500 ms
Shipping Box:
-
Dimensions: 8 1/2" L x 6" H x 6" D (215 mm x 152 mm x 152 mm)
-
Ship Weight: 5 lbs (2.3 kg)
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...