Description
The MTL4016 allows two switches or proximity detectors located in a hazardous area to control two safe-area loads each. It is designed for applications where the status of a sensor needs to be fed to two separate systems (e.g., control and shutdown).
Specifications
-
Number of Channels: Two
-
Output Type: Dual relay output
-
Relay Output Characteristics: Double-pole on/off, open when relay de-energized
-
Response Time: 2ms maximum
-
Contact Rating: 10W, 0.5A, 35V (DC)
-
Contact Life Expectancy: 10⁶ operations at maximum load
-
Input Voltage: 7.0V – 9.0V DC from 1kΩ
-
Output Characteristics:
- Outputs closed if >2.1mA in sensor circuit
- Outputs open if <1.2mA in sensor circuit
-
Hysteresis: 200μA (650Ω) nominal
-
Power Requirement:
- 50mA at 24V DC
- 60mA at 20V DC
- 45mA at 35V DC
-
Power Dissipation:
-
Safety Description: 10.5V, 800Ω, 14mA FM entity parameters
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...