The analog I/O modules (with HART communication function) communicate with field devices and store analog data and HART variables in the Input/Output image area in the communication module.
An FCS refers to and sets the Input/Output image by accessing the analog I/O modules (with HART communication function).
The FCS utilizes the field device data via I/O terminals of the function block in the same way as other analog/digital I/O signals.
Technical Specifications for Honeywell AAI143 Module:
-
Model: AAI143
-
Number of Input Channels: 16, isolated
-
Input Signal: 4 to 20 mA
-
Allowable Input Current: 24 mA
-
Withstanding Voltage (Between Input and System): 1500 V AC, for 1 minute
-
Input Resistance (Power ON):
- At 20 mA: 270 Ω
- At 4 mA: 350 Ω
-
Input Resistance (Power OFF): 500 kΩ or larger
-
Accuracy: ±16 µA
-
Data Update Period: 10 ms
-
Transmitter Power Supply:
- Minimum: 19.0 V (at 20 mA)
- Maximum: 25.5 V (at 0 mA, output current limit: 25 mA)
-
Setting of 2-wire or 4-wire Transmitter: For each channel by setting pin
-
Drift due to Ambient Temperature Change: ±16 µA/10˚C
-
Maximum Current Consumption:
- 230 mA (5 V DC)
- 540 mA (24 V DC)
-
Weight: 0.3 kg
-
External Communication: Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)
-
HART Communication: Available
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...